Smoke Management: Staircase Pressurization Calculations

Contents

Table of Contents

Staircase Pressurization

A type of smoke-control system in which stair shafts are mechanically pressurized, with respect to the fire area, with outdoor air to keep smoke from contaminating them during a fire incident.

Staircase Pressurization – Applications

Staircase pressurization systems are commonly used in:

  • High-rise residential buildings
  • Commercial office buildings
  • Hotels and hospitals
  • Shopping malls
  • Other buildings where protected escape staircases are required

NFPA 101 defines a high-rise building based on the height of an occupiable story above the lowest level of fire department vehicle access, using a threshold of more than 75 ft (23 m). Actual smoke-control requirements depend on the adopted code, building occupancy, and local authority requirements.

Types of Staircase Pressurization Systems

Single-Point Injection

In a single-point injection system, pressurization air is supplied to the staircase at one location, often near the bottom or another location determined by the design.

This arrangement may be suitable for shorter stairwells, subject to the applicable code and the results of the pressure and airflow calculations.

Multiple-Point Injection

In a multiple-point injection system, pressurization air is supplied at several levels of the staircase through strategically located supply points.

This arrangement can help distribute air more evenly throughout taller stairwells and address pressure variations caused by stack effect and leakage.

The required injection arrangement must be established through engineering calculations and the applicable project requirements. A height of 30.5 m is sometimes

used as a design criterion, but it should not be treated as a universal requirement without checking the governing standard.

How Does Staircase Pressurization Work?

When a fire occurs, the fire alarm system activates the staircase pressurization system according to the approved cause-and-effect sequence.

The pressurization fan draws outdoor air through a suitable intake and supplies it to the staircase through a duct or injection arrangement.

The supplied air creates a positive pressure within the staircase relative to the fire-affected corridor or adjacent space.

Smoke can otherwise enter through leakage paths, including gaps around doors, construction joints, and other openings. When staircase doors open, the pressure difference changes, so the system must be designed for the required combination of open and closed doors.

Primary Objective of Staircase Pressurization

The primary objective is to maintain a protected escape route by limiting smoke infiltration into the staircase during a fire emergency.

A properly designed system should:

  • Maintain the required pressure difference under specified operating conditions.
  • Limit smoke migration into the escape staircase.
  • Avoid excessive door-opening forces.
  • Account for leakage, open doors, and building pressure effects.
  • Operate reliably in coordination with the fire alarm and other smoke-control systems.

💡

What is the pressure difference that has to be maintained between corridor and staircase ?

12.5 Pa (sprinklered building)

Formula:

QT  =QL  + QO

‍