HVAC: FAHU

Contents

Table of Contents

What is FAHU?

A Fresh Air Handling Unit (FAHU) is a type of air handling unit that draws in outdoor air through an intake vent, filtering and treating it before distributing it throughout the indoor space.

It is designed to condition and distribute air to maintain indoor comfort and air quality.

Working principle:

  1. Air Intake: The FAHU draws in fresh outdoor air through an intake vent.‍
  2. Filtration: The incoming air passes through filters that remove dust, particles, and other contaminants. This is critical to ensure that the delivered air is clean and safe to breathe.‍
  3. Cooling: After filtration, the air passes over the cooling coils. These coils contain a cooling medium, typically chilled water or refrigerant, depending on the system design.As the air passes over the chilled coils, its temperature decreases.‍
  4. Air Distribution: Once the air has been cooled and conditioned, it is distributed into the building through a system of ducts and vents.‍
  5. Exhaust: The overall ventilation system may also include an exhaust system to remove stale indoor air and help maintain the required building pressure balance.

What is Energy Recovery Ventilation?

In HVAC systems, Energy Recovery Ventilation (ERV) is a process that uses energy from exhaust air to precondition incoming outdoor ventilation air.

ERV systems help save energy and may reduce the cooling and heating loads on mechanical equipment.

A heat recovery wheel, also known as a rotary heat exchanger or enthalpy wheel, is a device often used in HVAC systems to recover energy from exhaust air. It is an example of how HVAC systems can be designed to improve energy efficiency and sustainability.

The heat recovery wheel is located in the air streams of both the exhaust air leaving the building and the fresh air entering the FAHU. The wheel rotates slowly between these two air streams, transferring heat and, in the case of an enthalpy wheel, moisture.

Working principle:

  1. Exhaust Air: The exhaust air passes over one half of the heat recovery wheel, transferring heat and, where applicable, moisture to the wheel material.‍
  2. Rotation: The wheel rotates, carrying the energy stored in its material from the exhaust air stream to the fresh air intake stream.‍
  3. Fresh Air Intake: As warmer outdoor air passes over the conditioned portion of the wheel, energy is transferred to or from the wheel, depending on the operating conditions. This preconditions the incoming air before it reaches the cooling coil, reducing the cooling load.‍
  4. Continuation: The wheel continues to rotate, returning the material to the exhaust air stream so that the energy transfer cycle can repeat.

This process recovers energy from exhaust air that would otherwise be wasted, helping reduce the energy required to condition incoming outdoor air.

In addition to heat, some heat recovery wheels transfer moisture. These are known as enthalpy wheels. By recovering both sensible and latent energy, they can improve HVAC system efficiency.

Note: Rotary heat exchangers may experience some air carryover or leakage between the air streams. Purge sections and seals can reduce this transfer, but they do not necessarily eliminate it completely.

Heat Pipe Helps FAHU Save Big on Cooling Load

Heat pipes are devices used in Fresh Air Handling Units (FAHU) for energy recovery. They are particularly beneficial in climates with high cooling loads and a simultaneous need for dehumidification.

A heat pipe in a FAHU functions as a passive heat transfer device that can improve cooling system performance and efficiency. It has no moving parts and operates through evaporation and condensation of a working fluid.

In a FAHU, the heat pipe is typically divided into two sections: one located before the cooling coil (pre-cooling section) and the other after the cooling coil (reheat section).

The heat pipe pre-cools incoming fresh air before it reaches the cooling coil and reheats the air after it leaves the cooling coil.

The two sections are connected as a sealed system containing a working fluid that changes state depending on temperature and pressure conditions.

This process can improve both system efficiency and indoor comfort.

Working principle:

  1. Pre-Cooling: Warm outdoor air first passes over the pre-cooling section of the heat pipe.Heat from the incoming air is absorbed by the working fluid inside the heat pipe, causing it to evaporate. This cools the incoming air before it reaches the cooling coil, reducing the cooling coil load.‍
  2. Heat Transfer: The vapor carries the absorbed heat toward the reheat section due to the temperature difference between the two sections.‍
  3. Reheating: After passing over the cooling coil, the dehumidified air encounters the reheat section of the heat pipe. The working fluid releases the absorbed heat and condenses back into liquid form, slightly reheating the air. This reheating process can help control the supply air temperature while maintaining the moisture removal achieved by the cooling coil.‍
  4. Return Cycle: The condensed liquid returns to the pre-cooling section through gravity or a capillary structure, depending on the heat pipe design, and the cycle repeats.

This process improves the performance of the cooling system in several ways:

  • Pre-cooling reduces the load on the cooling coil, potentially saving energy.
  • Reheating helps control supply air temperature after dehumidification.
  • It can reduce overcooling when lower coil temperatures are required for moisture removal.

By improving the efficiency of the cooling process, heat pipes can provide significant benefits in cooling-focused FAHUs.

FAHU and Its Relationship with Relative Humidity

A Fresh Air Handling Unit (FAHU) can help maintain indoor relative humidity, particularly in hot and humid climates.

When outdoor air is cooled, its relative humidity may increase if no moisture is removed. However, when the air temperature falls below its dew point at the cooling coil, moisture condenses out of the air, reducing its moisture content.

Working principle:

  1. Cooling: Warm, humid outdoor air enters the FAHU and passes over the cooling coils.When the coil temperature is below the air's dew point, moisture condenses on the coil surface and is removed through the condensate drainage system. This dehumidifies the air and helps control indoor humidity.‍
  2. Reheating: If a heat pipe or another reheat arrangement is installed after the cooling coil, the dehumidified air can be reheated. Reheating lowers the relative humidity of the air because the air temperature increases while its moisture content remains approximately constant. It does not remove additional moisture by itself.‍
  3. Ventilation: The FAHU supplies fresh, conditioned outdoor air to the building. When coordinated with the building's exhaust and return-air arrangements, it helps maintain indoor air quality and humidity. The final humidity level depends on outdoor conditions, cooling coil performance, airflow, moisture loads, and the overall HVAC system design.